DN50 - DN300 (2" - 12")
ANSI Flanged
Aluminium, Nodular Iron, Cast Steel, SS304, SS316, SS316L
Up to + 90β (=194β) @ 1.1 bar abs
API 2000, BS7244, and EN 12874 / ISO 16852
As federal, state and local air quality regulations become more stringent, incineration of gases becomes a more viable option rather than venting to atmosphere. In addition, there are regulations that require gas with any significant sour content be flared because of foul smell and toxicity. Companies that engage in this type of activity understandably have important safety concerns and protection against flashback in systems that contain flammable liquid products becomes a serious issue.
End-of-Line Flame arrestors are utilised in the following applications:
End of line or free vent flame arrestors allow free venting in combination with flame protection for vertical vent applications.They prevent flame propagation by absorbing and dissipating heat using spiral wound crimped ribbon 316Lss flame cells. The KSFE unit gives the protection needed. For sizes 4β and under after ignition of the out flowing gases a fusible element melts, the spring loaded cover automatically opens and the full surface of the flame arrestor is exposed so that the flame arrestor element will not attain the ignition temperature through heat absorption.
Selection Criteria
Flame propagation poses significant dangers to systems and personnel in industries worldwide. Careful consideration must be taken to determine whether to use a Deflagration Flame Arrestor or a Detonation Flame Arrestor. There are two basic determinations when evaluating the intended application:
First, determine the location of all potential ignition sources (i.e. flare, vacuum pump, blower, burner, lightning strike, static discharge, etc).
Second, evaluate the system to determine exactly what should be protected (i.e., the gas source, process component, personnel, upstream process facility, tank, etc.).
When you have determined the ignition source(s) and what is to be protected, the following parameters should be evaluated in order to determine the appropriate flame arrestment protective device:
All of these variables affect the design of the arrestor and can also affect the dynamics of flame propagation.
Inline and End of Line Deflagration Flame Arrester Applications
The inline flame arrestor and the end of line (free vent) arrestor are used to stop flame propagation of confined and unconfined low pressure deflagrations. They are typically used
for limited piping applications when the system operating pressure is near atmospheric levels.
Detonation Flame Arrester Applications
The detonation flame arrestor is an advanced technology flame arrestor. They are used to stop the high pressures and velocities associated with detonation. They stop confined and unconfined low and high pressure deflagrations, stable and overdriven detonations. Application parameters for the detonation flame arrestors far exceed those of flame arrestors for pipe lengths, configurations, system operating pressures, and flame stabilisation. Our flame arrestors are designed, manufactured and tested according to API2000, BS7244 and BSEN1287 test standards and codes.
System gas grouping
The type of gas in the system and itβs corresponding gas group determines the design of the arrestor element. The SS316L element must be designed to accommodate the specific gas group that could possibly ignite and propagate in the system. The available designs consist of International Electric Code (IEC) group gases into IIC, IIB, IIA and I, the National Electric Code (NEC) groups gases into A, B, C and D categories depending on the MESG value of the gas.